Currency
Feature
1. ZTE PSU-AC 30A Power Supply Equipped with 2*R4815G/R4815N(Power module), 1*SMU01C.
2. Comes with 2 PCS 4Pin Cable + 1 PCS AC Power Cable.
3. Supports 2 power supply devices.
4. Supports 1 set of power battery.
5. 1605W total available power supply.
6. Supports a wide voltage range of 85 V AC to 300 V AC.
7. Provides comprehensive battery management.
8. The SMU01C connects to the power and environment over YDN protocol and access network host over master/slave protocols.
9. Displays information on a liquid crystal display (LCD) and provides buttons for operations.
10. Supports electronic labels.
11. Rectifiers and the site monitoring unit (SMU) are hot-swappable.
12. Allows high-efficiency and standard-efficiency rectifiers with the same capacity to coexist.
13. The rectifier power factor is 0.99..
Operating temperature | -40ºC to +70ºC NOTE:The system can run for 8 hours at 70ºC |
Transportation temperature |
-40ºC to +70ºC |
Storage temperature | -40ºC to +70ºC |
Operating humidity | 5%–95% RH (non-condensing) |
Storage humidity | 5%–95% RH (non-condensing) |
Altitude | 0-4000 m When the altitude ranges from 2000 m to 4000 m, the operating temperature decreases by 1ºC for each additional 200m. |
Input mode | 230 V AC single-phase three-wire (L, N), compatible with 230 V AC dual-live-wire (L, L) |
Input frequency | 45–66 Hz (rated frequency: 50/60 Hz) |
Power factor | ≥ 0.99 (100% load) |
Output voltage range | -42 V DC- -58 V DC |
Default output voltage | -53.5 V DC |
Maximum output power | 2000 W |
Regulated voltage precision |
≤ ±0.6% |
Peak-to-peak noise voltage |
≤ 200 mV (0–20 MHz) |
AC input overvoltage protection threshold |
Overvoltage protection is performed when the single-phase AC input voltage exceeds the AC input overvoltage protection threshold (300 V AC by default). |
AC input overvoltage recovery threshold |
When the voltage is restored to 290 V AC, the output resumes. |
AC input undervoltage protection threshold |
Undervoltage protection is performed when the single-phase AC input voltage is below the AC input undervoltage protection threshold (80 V AC by default). |
AC input undervoltage recovery threshold |
When the voltage is restored to 85 V AC, the output resumes. |
DC output overvoltage protection threshold |
-58.5 V DC to -60.5 V DC |
Safety and regulatory design |
Complies with IEC/EN60950-1 and passes TUV and CE. |
Mean time between failures (MTBF) |
250,000 hours |
Dimensions (H x W x D) | 43.6 mm x 442 mm x 255 mm |
Weight | ≤10 kg (with rectifiers) |
Protection level | IP20 |
Installation mode | Adapts to 19-inch cabinets and ETSI cabinets by using different types of mounting ears |
Maintenance mode | Maintained from the front |
Thanks for subscribing!