Huawei ETP4830-A1 30A Power Supply 
Huawei ETP4830-A1 30A Power Supply 
Huawei ETP4830-A1 30A Power Supply 
Huawei ETP4830-A1 30A Power Supply 
Huawei ETP4830-A1 30A Power Supply 
Huawei ETP4830-A1 30A Power Supply 
Huawei ETP4830-A1 30A Power Supply 

Huawei ETP4830-A1 30A Power Supply

Get Wholesale Price

Product Testing

We test products one by one. We test product functionality by simulating real-world usage scenarios to ensure smooth operation.

One-stop Service

Our products include optical fiber equipment, optical cable, accessories, tools, etc., whether you are a wholesaler, distributor, engineer, ISP, we can meet your needs.

14 months Warranty

Our warranty is above industry standards, up to 14 months. This is based on our confidence in the quality of our products and we want to give our customers more protection

Feature
1. ZTE PSU-AC 30A Power Supply Equipped with 2*R4815G/R4815N(Power module), 1*SMU01C.

2. Comes with 2 PCS 4Pin Cable + 1 PCS AC Power Cable.

3. Supports 2 power supply devices.

4. Supports 1 set of power battery.

5. 1605W total available power supply.

6. Supports a wide voltage range of 85 V AC to 300 V AC.

7. Provides comprehensive battery management.

8. The SMU01C connects to the power and environment over YDN protocol and access network host over master/slave protocols.

9. Displays information on a liquid crystal display (LCD) and provides buttons for operations.

10. Supports electronic labels.

11. Rectifiers and the site monitoring unit (SMU) are hot-swappable.

12. Allows high-efficiency and standard-efficiency rectifiers with the same capacity to coexist.

13. The rectifier power factor is 0.99..

Operating temperature -40ºC to +70ºC
NOTE:The system can run for 8 hours at 70ºC
Transportation
temperature
-40ºC to +70ºC
Storage temperature -40ºC to +70ºC
Operating humidity 5%–95% RH (non-condensing)
Storage humidity 5%–95% RH (non-condensing)
Altitude 0-4000 m
When the altitude ranges from 2000 m
to 4000 m, the operating temperature
decreases by 1ºC for each additional 200m.
Input mode 230 V AC single-phase three-wire (L, N),
compatible with 230 V AC dual-live-wire (L, L)
Input frequency 45–66 Hz (rated frequency: 50/60 Hz)
Power factor ≥ 0.99 (100% load)
Output voltage range -42 V DC- -58 V DC
Default output voltage -53.5 V DC
Maximum output power 2000 W
Regulated voltage
precision
≤ ±0.6%
Peak-to-peak noise
voltage
≤ 200 mV (0–20 MHz)
AC input overvoltage
protection threshold
Overvoltage protection is performed when the single-phase AC input voltage exceeds the AC input overvoltage protection threshold
(300 V AC by default).
AC input overvoltage
recovery threshold
When the voltage is restored to 290 V AC, the output resumes.
AC input undervoltage
protection threshold
Undervoltage protection is performed when the single-phase AC input voltage is below the AC input undervoltage protection threshold (80 V AC by default).
AC input undervoltage
recovery threshold
When the voltage is restored to 85 V AC, the output resumes.
DC output overvoltage
protection threshold
-58.5 V DC to -60.5 V DC
Safety and regulatory
design
Complies with IEC/EN60950-1 and passes TUV and CE.
Mean time between
failures (MTBF)
250,000 hours
Dimensions (H x W x D) 43.6 mm x 442 mm x 255 mm
Weight ≤10 kg (with rectifiers)
Protection level IP20
Installation mode Adapts to 19-inch cabinets and ETSI cabinets by using different types of mounting ears
Maintenance mode Maintained from the front